PD4N-KNXs-ST
Product Information
- KNX occupancy detector with integrated KNX bus connector
- KNX Secure ready
- Parameterisation from ETS 5 for integration into KNX systems
- Individual adaption of detection sensitivity for each PIR sensor
- PIR sensors can be deactivated individually
- Direction of movement can be identified
- Mixed light measurement using internal, external and remote (optional) light sensors
- Intelligent semi-automatic mode, occupancy-independent regulating mode (photoelectric switch), full automatic mode
- 1 x Light (for regulating or switching), 1 x slave output, 3 separate HVAC-blocs
- Regulation of up to three lighting groups using offset (external influence possible)
- Short presence, self-adjusting follow-up time, corridor function
- Various locking functions
- Soft-start
- Recall of light scenes
- Deactivatable status indicators
- The product database for import into the ETS database can be downloaded from the B.E.G. homepage.
- Detection area can be extended thanks to master-slave-mode
- Extensive optimization options for light measurement
- Measured light value is communicated to the bus
- Adaption of dimming curve
- Bidirectionally remote control-capable with the IR adapter and the B.E.G. smartphone app
- PIN code
- IR remote control-capable via IR remote control (optionally)
- Programming button (phys. address) can be operated via remote control
- HVAC mode (0=automatic, 1=comfort, 2=stand-by, 3=economy, 4=antifreeze/heat protection)
- Manual influence via external KNX push buttons possible
- Function control (heartbeat, cyclical sending)
- Forced switch-off
- Intelligent central-off function
- Premonition of switch-off
- Burn-in function for fluorescent lamps selectable from 1h till 100h
- Behaviour upon bus voltage return definable at choice
- Variable safety pause after switching off the lights
- Typical applications:
monitoring of large areas like underground garages, gyms, warehouses, loading ramps, halls
Technical Data
- Voltage:
- via KNX BUS
- Dimensions:
- FM= Ø 106 x 55 mm
FC= Ø 106 x 74 mm - typ. power input:
- 12 mA
- Detection area:
- horizontal 360° (Ceiling mounting)
- Range:
- max. Ø 24 m across
max. Ø 8 m towards
max. Ø 6,4 m seated - Monitored area (tangential movement):
- 450 m² / 2,5 m mounting height
- Mounting height min./max./recommended:
- 2 m / 10 m / 2,5 m
- Degree / class of protection:
- FM= IP20 / Class III
FC= IP20 / Class III - Impact strength:
- IK04
- Ambient temperature:
- -25 °C to +55 °C
- Housing:
- polycarbonate, UV-resistant
- Number of light sensors:
- 2
- Number of PIR sensors:
- 4
- KNX TP 256:
- Yes
- Orientation light
- 5 – 100 % / OFF / 1 min – 255 min
- Night light:
- 5 – 100 %
- Brightness set value:
- 5 – 2000 Lux
Description
| Description | Colour | Part number | EAN number |
|---|---|---|---|
| PD4N-KNXs-ST-FM | white mat, similar to RAL9010 | 93515 | 4007529935154 |
| PD4N-KNXs-ST-FC | white mat, similar to RAL9010 | 93514 | 4007529935147 |